DC Inverter Outdoor units for 3-way MULTISET VRF systems
-
Wide operating range: up to -20°C
in heating mode, -10°C in cooling mod
-
Twin Rotary DC Inverter Compressor
+ Scroll compressor
-
Low sound level
-
Maximum total pipe lenght: 300m
-
"Long Life" and "Fault-Tolerant"
special control systems
|
- DC Inverter Outdoor units for 3-way MULTISET
VRF systems
- Automatic change-over between cooling and
heating modes for each indoor unit; this feature, based on the
three-way technology with heat recovery, allows a fully independent
operation of each indoor unit.
- R410A HFC refrigerant.
- Twin Rotary DC Inverter
compressor, highly efficient at low rotation frequencies, matching
with a Scroll Constant-Speed compressor.
- Fan with direct current
motor that allows a consumption reduction of about 50% and a speed
modulation up to 16 steps in spite of the usual 4 steps of the
alternate current motors; this performance increases the efficiency
of the thermodynamic system which is able to best adapt to the
variations of temperature and thermal load of the rooms .
- The use of a special oil
sensor allows, for the first time in the world, to keep under
control the lubrification of the mechanical parts of the compressor.
- Special air intakes and
Double Chamber construction technology allowed to unify the
dimensions of the units, making easy the closing up for multiple
installatios in which two units can be placed at a distance of only
10 cm one from the other, the smaller distance available.
- Low sound level thanks
to a special fan made of resin and a particular resin grille,
designed and used for these units in order to minimize air pressure
drops.
- New high efficiency
Cross-Arranged heat exchanger with three-way suction, divided in two
sections with double control of defrosting cycle.
- Pressure control
automatic and by software on PC.
- Pipe connession inside
the unit frame through a special space to be closed back when the
installation is finished.
- Equipped with "Fault-Tolerant" system granting
in multiple installations the operation of the air conditioning
system also in case of total stop of one condensing unit.
- Support to "Long-Life" system that, in
multiple installations, allows a cyclic use of the condensing units,
granting a balance of the compressors activity.
- "On Demand" feature allows to best use the
characteristics of DC Inverter technology, setting three different
levels of electric power on which are automatically based the
control microprocessors so that to achieve the maximum performances
with reduction of electric consumption.
- Wide range of outdoor air temperature :
Outdoor temperature: from – 10° C to + 43° C in cooling mode
Outdoor temperature: from – 20° C to + 15° C in heating
mode.
- Maximum lenght of the
refrigerant circuit extended to 300 m.
- The refrigerant circuit
doesn't require distribution apparatus downstream of the unit as it
can be realized with a tree structure using only the special
distributor accessories; this feature facilitates any type of system
widening, by adding both outdoor and indoor units.
- Three-phase autosense
power supply 380-415/3N/50Hz.
3-way MULTISET VRF OUTDOOR UNITS |
GRFMI3V 705 R7I |
GRFMI3V 905 R7I |
Features |
Unit |
Cooling |
Heating |
Cooling |
Heating |
Cooling /
Heating capacity |
kW |
22,40 |
25,00 |
28,00 |
31,50 |
BTU/h |
76.400 |
85.300 |
95.500 |
107.500 |
kcal/h |
19.270 |
21.500 |
24.080 |
27.090 |
E.E.R. / C.O.P. |
(kW/kW) |
3,78 |
4,09 |
3,45 |
3,95 |
Air flowrate (HS) |
m³/h |
9.000 |
9.600 |
Sound pressure level (normal/silent mode) |
dB(A) |
54,5/51,5 |
55/52 |
Power supply |
V/Ph/Hz |
400/3N/50 |
400/3N/50 |
Power input |
kW |
5,93 |
6,11 |
8,12 |
7,97 |
Compressor type |
|
Twin Rotary DCI+Scroll CS |
Twin Rotary DCI+Scroll CS |
Refrigerant type |
|
R410A |
R410A |
Liquid pipe diameter |
mm(inches) |
9,52(3/8") |
9,52(3/8") |
Gas pipe diameter (suction) |
mm(inches) |
19,05(3/4") |
22,22(7/8") |
Gas pipe diameter (discharge) |
mm(inches) |
15,88(5/8") |
19,05(3/4") |
Max. total pipe
lenght |
m |
300 |
300 |
Refrigerant standard charge |
Kg |
12,00 |
12,00 |
Refrigerant additional charge |
gr/m |
56 |
56 |
Max. height between
units (O.U.on top) |
m |
50 |
50 |
Max. height between
units (I.U.on top) |
m |
40 |
40 |
Net weight O.U. |
Kg |
290 |
290 |
Net dimension O.U. (H./W./D.) |
mm |
1.887x890x890(+60) |
1.887x890x890(+60) |
3-way MULTISET VRF OUTDOOR UNITS |
GRFMI3V 1155 R7I |
GRFMI3V 1305 R7I |
GRFMI3V 1405 R7I |
Features |
Unit |
Cooling |
Heating |
Cooling |
Heating |
Cooling |
Heating |
Cooling /
Heating capacity |
kW |
33,50 |
37,50 |
40,00 |
45,00 |
45,00 |
50,00 |
BTU/h |
114.300 |
128.000 |
136.500 |
153.600 |
153.600 |
170.600 |
kcal/h |
28.810 |
32.250 |
34.400 |
38.700 |
38.700 |
43.000 |
E.E.R. / C.O.P. |
(kW/kW) |
3,41 |
3,81 |
3,45 |
3,91 |
3,38 |
3,79 |
Air flowrate (HS) |
m³/h |
10.800 |
12.000 |
13.200 |
Sound pressure level (normal/silent mode) |
dB(A) |
56/53 |
60/57 |
61/58 |
Power supply |
V/Ph/Hz |
400/3N/50 |
400/3N/50 |
400/3N/50 |
Power input |
kW |
9,82 |
9,84 |
11,6 |
11,5 |
13,3 |
13,2 |
Compressor type |
|
Twin Rotary DCI + Scroll CS |
Twin Rotary DC I+Scroll CS |
Twin Rotary DC I+Scroll CS |
Refrigerant type |
|
R410A |
R410A |
R410A |
Liquid pipe diameter |
mm(inches) |
12,70(1/2") |
12,70(1/2") |
12,70(1/2") |
Gas pipe diameter (suction) |
mm(inches) |
25,40(1") |
25,40(1") |
28,58(1-1/8") |
Gas pipe diameter (discharge) |
mm(inches) |
19,05(3/4") |
22,22(7/8") |
22,22(7/8") |
Max. total pipe
lenght |
m |
300 |
300 |
300 |
Refrigerant standard charge |
Kg |
12,00 |
15,00 |
15,00 |
Refrigerant additional charge |
gr/m |
128 |
128 |
128 |
Max. height between
units (O.U.on top) |
m |
50 |
50 |
50 |
Max. height between
units (I.U.on top) |
m |
40 |
40 |
40 |
Net weight O.U. |
Kg |
290 |
350 |
350 |
Net dimension O.U. (H./W./D.) |
mm |
1.887x890x890(+60) |
1.887x890x890(+60) |
1.887x890x890(+60) |
|
|
-
3-way Outdoor units
2-way Outdoor units
Miniset Outdoor units
Indoor units

 |