Technibel

  • DC Inverter Outdoor units for 3-way MULTISET VRF systems
  • Wide operating range: up to -20°C
    in heating mode, -10°C in cooling mod
  • Twin Rotary DC Inverter Compressor
    + Scroll compressor
  • Low sound level
  • Maximum total pipe lenght: 300m
  • "Long Life" and "Fault-Tolerant"
    special control systems
  • DC Inverter Outdoor units for 3-way MULTISET VRF systems
  • Automatic change-over between cooling and heating modes for each indoor unit; this feature, based on the three-way technology with heat recovery, allows a fully independent operation of each indoor unit.
  • R410A HFC refrigerant.
  • Twin Rotary DC Inverter compressor, highly efficient at low rotation frequencies, matching with a Scroll Constant-Speed compressor.
  • Fan with direct current motor that allows a consumption reduction of about 50% and a speed modulation up to 16 steps in spite of the usual 4 steps of the alternate current motors; this performance increases the efficiency of the thermodynamic system which is able to best adapt to the variations of temperature and thermal load of the rooms .
  • The use of a special oil sensor allows, for the first time in the world, to keep under control the lubrification of the mechanical parts of the compressor.
  • Special air intakes and Double Chamber construction technology allowed to unify the dimensions of the units, making easy the closing up for multiple installatios in which two units can be placed at a distance of only 10 cm one from the other, the smaller distance available.
  • Low sound level thanks to a special fan made of resin and a particular resin grille, designed and used for these units in order to minimize air pressure drops.
  • New high efficiency Cross-Arranged heat exchanger with three-way suction, divided in two sections with double control of defrosting cycle.
  • Pressure control automatic and by software on PC.
  • Pipe connession inside the unit frame through a special space to be closed back when the installation is finished.
  • Equipped with "Fault-Tolerant" system granting in multiple installations the operation of the air conditioning system also in case of total stop of one condensing unit.
  • Support to "Long-Life" system that, in multiple installations, allows a cyclic use of the condensing units, granting a balance of the compressors activity.
  • "On Demand" feature allows to best use the characteristics of DC Inverter technology, setting three different levels of electric power on which are automatically based the control microprocessors so that to achieve the maximum performances with reduction of electric consumption.
  • Wide range of outdoor air temperature :
    Outdoor temperature: from  – 10° C to + 43° C in cooling mode
    Outdoor temperature: from  – 20° C to + 15° C in heating mode.
  • Maximum lenght of the refrigerant circuit extended to 300 m.
  • The refrigerant circuit doesn't require distribution apparatus downstream of the unit as it can be realized with a tree structure using only the special distributor accessories; this feature facilitates any type of system widening, by adding both outdoor and indoor units.
  • Three-phase autosense power supply 380-415/3N/50Hz.
3-way MULTISET VRF OUTDOOR UNITS
GRFMI3V 705 R7I
GRFMI3V 905 R7I
Features
Unit
Cooling
Heating
Cooling
Heating
Cooling / Heating capacity
kW
22,40
25,00
28,00
31,50
BTU/h
76.400
85.300
95.500
107.500
kcal/h
19.270
21.500
24.080
27.090
E.E.R. / C.O.P.
(kW/kW)
3,78
4,09
3,45
3,95
Air flowrate (HS)
m³/h
9.000
9.600
Sound pressure level (normal/silent mode)
dB(A)
54,5/51,5
55/52
Power supply
V/Ph/Hz
400/3N/50
400/3N/50
Power input
kW
5,93
6,11
8,12
7,97
Compressor type
Twin Rotary DCI+Scroll CS
Twin Rotary DCI+Scroll CS
Refrigerant type
R410A
R410A
Liquid pipe diameter
mm(inches)
9,52(3/8")
9,52(3/8")
Gas pipe diameter (suction)
mm(inches)
19,05(3/4")
22,22(7/8")
Gas pipe diameter (discharge)
mm(inches)
15,88(5/8")
19,05(3/4")
Max. total pipe lenght
m
300
300
Refrigerant standard charge
Kg
12,00
12,00
Refrigerant additional charge
gr/m
56
56
Max. height between units (O.U.on top)
m
50
50
Max. height between units (I.U.on top)
m
40
40
Net weight O.U.
Kg
290
290
Net dimension O.U. (H./W./D.)
mm
1.887x890x890(+60)
1.887x890x890(+60)

3-way MULTISET VRF OUTDOOR UNITS
GRFMI3V 1155 R7I
GRFMI3V 1305 R7I 
GRFMI3V 1405 R7I
Features
Unit
Cooling
Heating
Cooling
Heating
Cooling
Heating
Cooling / Heating capacity
kW
33,50
37,50
40,00
45,00
45,00
50,00
BTU/h
114.300
128.000
136.500
153.600
153.600
170.600
kcal/h
28.810
32.250
34.400
38.700
38.700
43.000
E.E.R. / C.O.P.
(kW/kW)
3,41
3,81
3,45
3,91
3,38
3,79
Air flowrate (HS)
m³/h
10.800
12.000
13.200
Sound pressure level (normal/silent mode)
dB(A)
56/53
60/57
61/58
Power supply
V/Ph/Hz
400/3N/50
400/3N/50
400/3N/50
Power input
kW
9,82
9,84
11,6
11,5
13,3
13,2
Compressor type
Twin Rotary DCI + Scroll CS
Twin Rotary DC I+Scroll CS
Twin Rotary DC I+Scroll CS
Refrigerant type
R410A
R410A
R410A
Liquid pipe diameter
mm(inches)
12,70(1/2")
12,70(1/2")
12,70(1/2")
Gas pipe diameter (suction)
mm(inches)
25,40(1")
25,40(1")
28,58(1-1/8")
Gas pipe diameter (discharge)
mm(inches)
19,05(3/4")
22,22(7/8")
22,22(7/8")
Max. total pipe lenght
m
300
300
300
Refrigerant standard charge
Kg
12,00
15,00
15,00
Refrigerant additional charge
gr/m
128
128
128
Max. height between units (O.U.on top)
m
50
50
50
Max. height between units (I.U.on top)
m
40
40
40
Net weight O.U.
Kg
290
350
350
Net dimension O.U. (H./W./D.)
mm
1.887x890x890(+60)
1.887x890x890(+60)
1.887x890x890(+60)


 


User ID
Password
info