Hi-wall Terminal units for air/water
Chillers
and Heat Pumps
-
New flat design
-
Compact units
-
5 models, 4 sizes
-
Very low noise level
-
Same aesthetic for all models
-
Available with both infrared remote
controller and wired remote controller
|
- The MPW are hi-wall Terminal units especially
recommeded for rooms in which the floor must remain free or for water
distribution systems in false ceilings.
- Very low noise level.
- The units are available with infrared remote
controller or wired remote controllers, manual (RAB 30) or automatic (RCC 10
for MPW1/2/3/4B5B and RCC 20 for MPW1BE5B). The infrared remote
controller is provided in standard with the unit, the wired remote
controllers are available as accessories.
- The active carbon filter, available as
accessory, deodorises the ambient. It is added to the standard
air filter which retains dust.
- Application fields:
- offices
- meeting rooms
- commercial surfaces.
- Fonctions common to all hi-wall models:
- Cooling or heating by 2-pipe coil.
- Ventilation with integrated filtration.
MODELS |
MPW1 |
MPW 1 BE |
MPW2 |
MPW3 |
MPW4 |
Type |
|
2-pipe coils |
2-pipe + elec.
heating |
2-pipe coils |
2-pipe coils |
2-pipe coils |
Code - Model with infrared remote
controller |
|
MPW 1B5X |
- |
MPW 2B5X |
MPW 3B5X |
MPW 4B5X |
Code - Model without
infrared remote controller |
|
MPW 1B5B |
MPW 1BE5B |
MPW 2B5B |
MPW 3B5B |
MPW 4B5B |
|
|
|
|
|
|
|
Total cooling capacity (HS-LS) |
kW |
1,24-0,80 |
1,24-0,80 |
1,67- 0,96 |
3,17-1,91 |
3,67-2,62 |
Sensible cooling capacity (HS-LS) |
kW |
0,94-0,58 |
0,94-0,58 |
1,3-0,74 |
2,56-1,53 |
3,01-2,12 |
Heating capacity (HS-LS) |
kW |
1,72- 1,11 |
1,72- 1,11 |
2,38-1,49 |
4,5-2,7 |
5,5-3,7 |
Heating capacity by electric
heating |
kW |
- |
0,5 |
- |
- |
- |
Air flow (HS-LS) |
m3/h |
220-150 |
220-150 |
270-180 |
510-420-320 |
710-580-470 |
Water flow in cooling mode |
l/h |
215 |
215 |
290 |
545 |
630 |
Pressure drop on water in
cooling mode |
kPa |
16,1 |
16,1 |
27,2 |
29,4 |
35,1 |
Pressure drop on water in
heating mode |
kPa |
15,3 |
15,3 |
26,2 |
27,5 |
31,8 |
Power supply |
V/Ph/Hz |
230/1/50 |
230/1/50 |
230/1/50 |
230/1/50 |
230/1/50 |
Maximum power input |
kW |
0,025 |
0,525 |
0,025 |
0,07 |
0,08 |
Maximum running current |
A |
0,11 |
2,3 |
0,11 |
0,33 |
0,36 |
Hydraulic connection diameter |
inches |
1/2" G female |
1/2" G female |
1/2" G female |
1/2" G female |
1/2" G female |
Sound power level (HS-MS-LS) |
dB(A) |
44-37 |
44-37 |
45-35 |
58-52-46 |
62-56-50 |
Sound pressure level at 2 m (HS-MS-LS) |
dB(A) |
35-28 |
35-28 |
36-26 |
49-43-37 |
53-47-41 |
Net dimension (H./W./D.) |
mm |
270x805x177 |
270x805x177 |
270x805x177 |
285x995x206 |
285x995x206 |
Net weight |
Kg |
8 |
8 |
8 |
12 |
12 |
|
|
Infrared remote control with
temperature sensor inside
Manual wired remote controller
70250076 (RAB 30)

Automatic wired remote controller
70250051(RCC 10)-70250052 (RCC 20)
|