Cassette Terminal units for air/water
Chillers
and Heat Pumps
-
5 sizes - 2 and 4-pipe coils
-
Cooling capacity: from 2150 to 9920 W
-
Heating capacity: from 2830 to 11700 W
-
Available with both infrared remote
controller and wired remote controller
|
- The CWX units are water chilled Terminal units
designed for the air conditioning of commercial premises such as shops,
offices, stores, meeting rooms, commercial surfaces, hotels.
- Their installation in the false ceiling allow
to hide the supply pipes, leaving wall spice completely clear.
The models CWX3 and CWX5 can be extremely discreetly installed,
their dimension being exactly the same as those of the false ceiling
panel (600mmx600mm).
- Available versions: 2-pipe coils, 2 pipes/2
wires and 4-pipe coils.
- Very low noise level.
- The air diffusion is obtained on the 4 sides
of the grill.
- The units are available with infrared remote
controller or wired remote controllers, manual (RAB 30) or automatic
(RCC 10 for CWX3/5/6/8/10B5B and RCC 20 for CWX3/5 BE5B/BW5B).
The infrared remote controller is provided in standard with the unit,
the wired remote controllers are available as accessories.
- These cassettes are fitted with a manual air
vent and a condensate drain pump.
- Fonctions common to all cassette models:
- Cooling or heating by 2-pipe coil.
- Ventilation with integrated filtration.
MODELS |
CWX 3 B |
CWX 3 BE |
CWX 3 BW |
CWX 5 B |
CWX 5 BE |
CWX 5 BW |
Type |
|
2 -pipe coils |
2 pipes+el. heat. |
4-pipe coils |
2 -pipe coils |
2 pipes+el. heat. |
4-pipe coils |
Code - Model with
infrared remote controller |
|
CWX 3B5X |
- |
- |
CWX 5B5X |
- |
- |
Code grill - Model
with infrared remote controller |
|
K70N129 T |
- |
- |
K70N129 T |
- |
- |
Code - Model
without infrared remote controller |
|
CWX 3B5B |
CWX 3BE5B |
CWX 3BW5B |
CWX 5B5B |
CWX5BE5B |
CWX 5BW5B |
Code grill-Model
without infrared remote controller |
|
K70N090 T |
K70N090 T |
K70N090 T |
K70N090 T |
K70N090 T |
K70N090 T |
|
|
|
|
|
|
|
|
Total cooling
capacity (HS-MS-LS) |
kW |
2,6-2,35-2,15 |
2,08-1,88-1,72 |
2,08-1,88-1,72 |
4,7-4,1-3,6 |
4,23-3,69-3,24 |
3,76-3,28-2,88 |
Sensible cooling
capacity (HS-MS-LS) |
kW |
2,31-2,09-1,91 |
1,85-1,67-1,53 |
1,85-1,67-1,53 |
3,72-3,21-2,8 |
3,35-2,89-2,52 |
2,98-2,56-2,24 |
Heating capacity (HS-MS-LS) |
kW |
3,49-3,11-2,83 |
2,96-2,64-2,4 |
- |
5,7-4,85-4,35 |
5,13-4,37-3,92 |
- |
Heating capacity
by electric heating |
kW |
- |
1,25 |
- |
- |
2,5 |
- |
Heating capacity
additional coil (HS-MS-LS) |
kW |
- |
- |
1,51-1,34-1,22 |
- |
- |
2,33-1,98-1,78 |
Air flow (HS-MS-LS) |
m3/h |
520-460-400 |
520-460-400 |
520-460-400 |
750-630-530 |
750-630-530 |
750-630-530 |
Water flow in
cooling mode (HS) |
l/h |
447 |
358 |
358 |
808 |
728 |
647 |
Water flow
additional coil |
l/h |
- |
- |
108 |
- |
- |
167 |
Pressure drop on
water in cooling mode (HS) |
kPa |
22 |
22 |
22 |
42 |
42 |
42 |
Pressure drop on
water in heating mode (HS) |
kPa |
18 |
18 |
- |
33 |
33 |
- |
Pressure drop on
water additional coil (HS) |
kPa |
- |
- |
18 |
- |
- |
33 |
Power supply |
V/Ph/Hz |
230/1/50 |
230/1/50 |
230/1/50 |
230/1/50 |
230/1/50 |
230/1/50 |
Maximum power
input |
kW |
0,060 |
1,31 |
0,060 |
0,09 |
2,59 |
0,09 |
Maximum running
current |
A |
0,25 |
5,70 |
0,25 |
0,4 |
11,3 |
0,4 |
Hydraulic
connection diameter |
inches |
1/2" G female |
1/2" G female |
1/2" G female |
1/2" G female |
1/2" G female |
1/2" G female |
Sound power level
(HS-MS-LS) |
dB(A) |
46-44-41 |
46-44-41 |
46-45-42 |
56-51-48 |
56-51-48 |
56-51-48 |
Sound pressure
level at 2 m (HS-MS-LS) |
dB(A) |
37-35-32 |
37-35-32 |
37-36-33 |
47-42-39 |
47-42-39 |
47-42-39 |
Net dimension (H./W./D.) |
mm |
296x575x575 |
296x575x575 |
296x575x575 |
296x575x575 |
296x575x575 |
296x575x575 |
Net dimension
grill (H./W./D.) |
|
41x730x730 |
41x730x730 |
41x730x730 |
41x730x730 |
41x730x730 |
41x730x730 |
Net weight (grill
included) |
Kg |
21 |
21 |
21 |
23 |
23 |
23 |
MODELS |
CWX 6 |
CWX 8 |
CWX 10 |
Type |
|
2 -pipe coils |
2 -pipe coils |
2 -pipe coils |
Code - Model with
infrared remote controller |
|
CWX 6B5X |
CWX 8B5X |
CWX 10B5X |
Code grill - Model
with infrared remote controller |
|
K70N130T |
K70N131T |
K70N131T |
Code - Model
without infrared remote controller |
|
CWX 6B5B |
CWX 8B5B |
CWX 10B5B |
Code grill- Model
without infrared remote controller |
|
K70N094 T |
K70N095 T |
K70N095 T |
|
|
|
|
|
Total cooling
capacity (HS-MS-LS) |
kW |
6-5-4,2 |
8-6,5-5,5 |
9,92-8,09-6,23 |
Sensible cooling
capacity (HS-MS-LS) |
kW |
4,7-3,8-3,2 |
6,4-5,4-4,1 |
7,9-6,22-4,62 |
Heating capacity (HS-MS-LS) |
kW |
7,7-6,4-5,4 |
9,42-8,52-6,28 |
13-10,6-8,16 |
Air flow (HS-MS-LS) |
m3/h |
1300-1060-840 |
1270-1090-830 |
2270-1700-1220 |
Water flow in
cooling mode (HS) |
l/h |
1036 |
1380 |
1700 |
Pressure drop on
water in cooling mode (HS) |
kPa |
30 |
41 |
63 |
Pressure drop on
water in heating mode (HS) |
kPa |
30 |
39 |
60 |
Power supply |
V/Ph/Hz |
230/1/50 |
230/1/50 |
230/1/50 |
Maximum power
input |
kW |
0,120 |
0,120 |
0,18 |
Maximum running
current |
A |
0,5 |
0,5 |
0,8 |
Hydraulic
connection diameter |
inches |
3/4" G female |
3/4" G female |
3/4" G female |
Sound power level (HS-MS-LS) |
dB(A) |
55-48-51 |
50-46-37 |
57-49-43 |
Sound pressure
level at 2 m (HS-MS-LS) |
dB(A) |
46-42-39 |
41-37-28 |
48-40-34 |
Net dimension (H./W./D.) |
mm |
358x760x760 |
358x1050x760 |
358x1050x760 |
Net dimension
grill (H./W./D.) |
|
48x860x860 |
48x1150x860 |
48x1150x860 |
Net weight (grill
included) |
Kg |
28 |
36 |
36 |
|
|
Infrared remote control with
temperature sensor inside
Manual wired remote controller
70250076 (RAB 30)

Automatic wired remote controller
70250051(RCC 10)-70250052 (RCC 20)
|