Underceiling air conditioners for commercial applications
-
Heat pump version
-
Wide operating range, with outdoor air temperatures up to
-15°C, in both cooling
and heating modes
-
High efficiency DC Inverter technology
-
Ozone friendly refrigerant R410A
-
New centrifugal fan, for a better and low noise air diffusion.
|
- PAM DC Inverter technology ("pulse amplitude
modulation").
- Single-phase (230/1/50) power supply thanks to DC
Inverter technology low consumption.
- Dynamic refrigerant control by DC Inverter
compressor and circuit, electronic valve and fuzzy logic managed by
a powerful microprocessor.
- Special function during heat pump start-up and
defrosting cycle to avoid cool air emission in the room.
- Automatic change-over between cooling and heating
modes.
- Among the control units available for this kind
of indoor unit (all optional):
- the infrared remote control, equipped with a 24h digital
timer and a temperature sensor, granting automatically
the best comfort conditions ("I Feel" feature);
- a special wired controller with configuration, diagnostic and
weekly timer capabilities.
- Dry function.
- Night set back capability.
- New three-speed centrifugal fan by remote control,
granting a better and low noise air diffusion.
- Horizontal flap swinging or to be set to a fixed
position by remote control.
- Vertical flap by manual control.
- Anti-mould and anti-bacteria washable filters.
- Auto restart after a power supply black out.
- Electronic protection against over-pressures.
- Twin Rotary DC Inverter compressor.
MODELS |
SPFI 255 R5 |
SPFI 365 R5 |
Indoor unit |
|
SPAFP 255 R5 I |
SPAFP 365 R5 I |
Outdoor unit |
230/1/50 |
GRFP 255 R5 I |
GRFP 365 R5 I |
Features |
|
Cooling |
Heating |
Froid |
Chaud |
Cooling/Heating capacity |
kW |
7,10 (2,2-8,0) |
8,00 (2,2-9,0) |
10,00 (2,2-11,2) |
11,20 (2,2-12,50) |
BTU/h |
24.000 |
27.000 |
34.000 |
38.000 |
kcal/h |
6.100 |
6.880 |
8.600 |
9.630 |
Energy efficiency class |
ABCDEFG |
B |
B |
B |
A |
E.E.R./C.O.P. |
(kW/kW) |
3,02 |
3,56 |
3,04 |
3,67 |
Air flowrate (HS-MS-LS) |
m³/h |
1.098-900-840 |
1.650-1.380-1.200 |
Dehumidification |
l/h |
3,0 |
3,9 |
Fan speeds (I.U. / O.U.) |
n° |
3 + Auto / 3 (Auto) |
3 + Auto / 3 (Auto) |
Sound pressure level I.U. (HS-MS-LS)
at 2 m |
dB(A) |
38-36-33 |
41-38-35 |
Sound power level I.U. (HS-MS-LS) |
dB(A) |
46-44-41 |
49-46-43 |
Sound pressure level O.U. (HS) at 4 m |
dB(A) |
49 |
52 |
Sound power level O.U. (HS) |
dB(A) |
69 |
72 |
Power input / Running current |
kW / A |
2,35 / 12,8 |
2,25 / 12,3 |
3,29 / 16,2 |
3,67 / 15,1 |
Annual energy consumption in Cooling
mode - (500h) |
kWh |
1.175 |
- |
1.645 |
- |
Compressor type |
|
DCInverter Twin Rotary |
DCInverter Twin Rotary |
Refrigerant type |
|
R410A |
R410A |
Liquid pipe diameter |
mm(inch) |
9,52(3/8") |
9,52(3/8") |
Gas pipe diameter |
mm(inch) |
15,88(5/8") |
15,88(5/8") |
Max. pipe lenght with gas standard
charge |
m |
30 |
30 |
Max. pipe lenght with gas
additional charge |
m |
50 |
50 |
Gas additional charge |
gr/m |
40 |
40 |
Max. height between units |
m |
50 / 30 |
50/30 |
Internal diameter of condensate
drain pipe |
mm |
26 |
26 |
Net weight I.U. / O.U. |
Kg |
25/58 |
33/65 |
Net dimension I.U. (H./W./D.) |
mm |
210x1.180x680 |
210x1.595x680 |
Net dimension O.U. (H./W./D.) |
mm |
780x940x340 |
780x940x340 |
The technical data
here indicated are in compliance with the European standard EN14511
- Directive 2002/31/EC
|
|
Infrared remote control (optional)
Infrared remote control + special
wall receiver (optional)

Standard wired remote control (optional)
Simplified wired remote control (optional) |