Technibel


  • Underceiling air conditioners for commercial applications
  • Heat pump version
  • Wide operating range, with outdoor air temperatures up to -15°C, in both cooling
    and heating modes
  • High efficiency DC Inverter technology
  • Ozone friendly refrigerant R410A
  • New centrifugal fan, for a better and low noise air diffusion.
  • PAM DC Inverter technology ("pulse amplitude modulation").
  • Single-phase (230/1/50) power supply thanks to DC Inverter technology low consumption.
  • Dynamic refrigerant control by DC Inverter compressor and circuit, electronic valve and fuzzy logic managed by a powerful microprocessor.
  • Special function during heat pump start-up and defrosting cycle to avoid cool air emission in the room.
  • Automatic change-over between cooling and heating modes.
  • Among the control units available for this kind of indoor unit (all optional):
    -  the infrared remote control, equipped with a 24h digital timer and a temperature sensor, granting automatically
       the best comfort conditions ("I Feel" feature);
    - a special wired controller with configuration, diagnostic and weekly timer capabilities.
  • Dry function.
  • Night set back capability.
  • New three-speed centrifugal fan by remote control, granting a better and low noise air diffusion.
  • Horizontal flap swinging or to be set to a fixed position by remote control.
  • Vertical flap by manual control.
  • Anti-mould and anti-bacteria washable filters.
  • Auto restart after a power supply black out.
  • Electronic protection against over-pressures.
  • Twin Rotary DC Inverter compressor.
MODELS 
SPFI 255 R5
SPFI 365 R5
Indoor unit
SPAFP 255 R5 I
SPAFP 365 R5 I
Outdoor unit
230/1/50
GRFP 255 R5 I
GRFP 365 R5 I
Features
Cooling
Heating
Froid
Chaud
Cooling/Heating capacity
kW
7,10 (2,2-8,0)
8,00 (2,2-9,0)
10,00 (2,2-11,2)
11,20 (2,2-12,50)
BTU/h
24.000
27.000
34.000
38.000
kcal/h
6.100
6.880
8.600
9.630
Energy efficiency class
ABCDEFG
B
B
B
A
E.E.R./C.O.P.
(kW/kW)
3,02
3,56
3,04
3,67
Air flowrate (HS-MS-LS)
m³/h
1.098-900-840
1.650-1.380-1.200
Dehumidification
l/h
3,0
3,9
Fan speeds (I.U. / O.U.)
3 + Auto / 3 (Auto)
3 + Auto / 3 (Auto)
Sound pressure level I.U. (HS-MS-LS) at 2 m
dB(A)
38-36-33
41-38-35
Sound power level I.U. (HS-MS-LS)
dB(A)
46-44-41
49-46-43
Sound pressure level O.U. (HS) at 4 m
dB(A)
49
52
Sound power level O.U. (HS)
dB(A)
69
72
Power input / Running current
kW / A
2,35 / 12,8
2,25 / 12,3
3,29 / 16,2
3,67 / 15,1
Annual energy consumption in Cooling mode - (500h)
kWh
1.175
-
1.645
-
Compressor type
DCInverter Twin Rotary
DCInverter Twin Rotary
Refrigerant type
R410A
R410A
Liquid pipe diameter
mm(inch)
9,52(3/8")
9,52(3/8")
Gas pipe diameter
mm(inch)
15,88(5/8")
15,88(5/8")
Max. pipe lenght with gas standard charge
m
30
30
Max. pipe lenght with gas additional charge
m
50
50
Gas additional charge
gr/m
40
40
Max. height between units
m
50 / 30
50/30
Internal diameter of condensate drain pipe
mm
26

26

Net weight I.U. / O.U.
Kg
25/58
33/65
Net dimension I.U. (H./W./D.)
mm
210x1.180x680
210x1.595x680
Net dimension O.U. (H./W./D.)
mm
780x940x340
780x940x340

The technical data here indicated are in compliance with the European standard EN14511 - Directive 2002/31/EC


 

Infrared remote control (optional)

Infrared remote control  + special wall receiver (optional)

Standard wired remote control (optional)

Simplified wired remote control (optional)


User ID
Password
info