Technibel

  • Outdoor units for Multi-simultaneous
    systems
  • Wide operating range, with outdoor
    air temperatures up to -15°C,
    in both cooling and heating modes
  • High efficiency Twin Rotary DC Inverter compressor
  • Maximum total pipe lenght: 50m
  • 1 Outdoor unit is matchable with 2, 3 or 4 indoor units (hi-wall, floor, floor/ceiling, underceiling, cassette and ducted) operating simultaneously.
  • Particularly suitable for big shops, halls of hospital, common rooms of the establishments of health or old people's homes, rooms of conference, rooms of restaurant, department stores or commercial surfaces.  The installation of more indoor units in one only big room allows a better diffusion of the conditioned air.
  • The Multi-simultaneous system control allows a sophisticated control of multi-simultaneous configurations by zones.
  • Single-phase (230/1/50) power supply, thanks to DC Inverter technology low consumption.
  • Dynamic refrigerant control by DC Inverter compressor and circuit, electronic valve and fuzzy logic managed by a powerful microprocessor.
OUTDOOR UNITS for MULTI-SIMULTANEOUS SYSTEMS   HEAT PUMP MODELS
GRFP 255 R5I
GRFP 365 R5I
GRFP 485 R5I
Features
Unit
Cooling
Heating
Cooling
Heating
Cooling
Heating
Connectable indoor units
no.
2
2 à 4
Cooling / Heating capacity nom. (min.-max.)
kW
7,1 (2,2-8,0)
8,0(2,2-9,0)
10 (2,2-11,2)
11,2 (2,2-12,5)
12,5 (2,7-14)
14 (2,7-16)
BTU/h
24.210
27.280
34.100
38.190
42.630
47.740
kcal/h
6.110
6.880
8.600
9.630
10.750
12.040
Air flowrate (HS)
m3/h
3.000
3.300
6.000
Fan speeds O.U.
3
3
3
Power supply
V/Ph/Hz
230/1/50
230/1/50
230/1/50
Compressor type
Twin Rotary (DC inverter)
Twin Rotary (DC inverter)
Twin Rotary (DC inverter)
Refrigerant type
R410A
R410A
R410A
Liquid pipe diameter
mm(inches)
9,52(3/8")
9,52(3/8")
9,52(3/8")
Gas pipe diameter
mm(inches)
15,88(5/8")
15,88(5/8")
15,88(5/8")
Max. total pipe lenght
m
50
50
50
Max. height between units (Outdoor on top)
m
30
30
30
Max. height between units (Indoor on top)
m
15
15
15
Max. height between indoor units
m
0,5
0,5
0,5
Sound pressure level O.U. (HS) at 4 m
dB(A)
49
52
53
Sound power level O.U. (HS)
dB(A)
69
72
73
Net weight O.U.
Kg
58
65
100
Net dimension O.U. (H./W./D.)
mm
780x940x340
780x940x340
1230x940x340
The technical data here indicated are in compliance with the European standard EN14511 - Directive 2002/31/EC


 