8 models from 21 to 78 kW
-
Very compact units
-
Refrigerant R407C
-
Complete hydraulic equipment
incorporated
-
Electronic control system
|
- Chillers intended for heating and air-conditioning
of commercial buildings.
- Compact units to be installed outside.
- Ozone friendly refrigerant R407C for the respect of the environment.
- Higher coefficients of performances thanks to
the augmentation of the available hydraulic pressure.
- Scroll compressor with
sound insulation, high performance fin heat exchanger with
protection grill, axial fan motor with variable speed control
and heat protection, heat exchanger with AISI 316 stainless steel
plates and heat insulation, etc.
- Units ready to operate, with hydraulic
equipment incorporated : 3-speed circulating pump, expansion
tank, safety valve, air bleed valve, water pressure control,
hydraulic filter.
- Complete equipment: the chillers CHGV are
equipped with the following safety systems: high and low pressure
switch, water flow switch, anti-freeze safety.
- Proportional head pressure control.
- Electronic control by microprocessor (with keypad)
which optimizes the operation of the Chiller and grants the
following functions:
- Temperature control of hot water and cold water
- Self-adapting algorithm allowing the reduction
of the water volume (elimination of the buffer receiver vessel)
- Control of the operating parameters
- Automatic control of the circulating pump (anti-freeze and
anti-seize fonction)
- Counting of the operating time of compressor and circulator
- Defrosting adjusted according to the outdoor temperature
- Condensation pressure control
- Alarm management
- External communication via a serial inerface (Protocol
Modbus) (accessory)
- Output for controlling an additional
electronic device (not supplied).
- Phase sequence tester.
- Additional electrical heating (in option).
- Easy access to all components.

MODELS |
CHGV 22 |
CHGV 25 |
CHGV 32 |
CHGV 40 |
Outdoor unit
Features |
400/3N/50 |
CHG 227 V |
CHG 257 V |
CHG 327 V |
CHG 407 V |
Unit |
Cooling |
Cooling |
Cooling |
Cooling |
Cooling capacity |
kW |
20,7 |
23,8 |
31 |
39 |
Power input |
kW |
8,3 |
10,4 |
13,4 |
14,8 |
E.E.R. |
(kW/kW) |
2,49 |
2,29 |
2,31 |
2,64 |
Water flow |
m³/h |
3,56 |
4,2 |
5,33 |
6,71 |
Available head pump |
Kpa |
210 |
170 |
200 |
135 |
Refrigerant type |
|
R407C |
R407C |
R407C |
R407C |
Nb of refrigerant circuits |
no. |
1 |
1 |
1 |
1 |
Nb of compressors |
no. |
1 |
1 |
1 |
1 |
Expansion tank capacity |
l |
8 |
8 |
8 |
8 |
Water connector diameter
- male |
(inches) |
1" 1/4 |
1" 1/4 |
1" 1/4 |
1" 1/4 |
Sound pressure level (HS) at 10 m** |
dB(A) |
51 |
50 |
52 |
54 |
Sound power level (HS) |
dB(A) |
79 |
78 |
80 |
82 |
Net dimension (H./W./D.) |
mm |
1175x975x1050 |
1175x975x1050 |
1175x975x1050 |
1425x975x1050 |
Net weight |
Kg |
292 |
295 |
317 |
353 |
MODELS |
CHGV 50 |
CHGV 64 |
CHGV 72 |
CHGV 80 |
Outdoor unit
Features |
400/3N/50 |
CHG 507 V |
CHG 647 V |
CHG 727 V |
CHG807 V |
Unit |
Cooling |
Cooling |
Cooling |
Cooling |
Cooling capacity |
kW |
47,6 |
62 |
67 |
78 |
Power input |
kW |
20,6 |
26,4 |
28,8 |
29,4 |
E.E.R. |
(kW/kW) |
2,31 |
2,35 |
2,33 |
2,65 |
Water flow |
m³/h |
8,21 |
10,65 |
11,5 |
13,43 |
Available head pump |
Kpa |
220 |
160 |
180 |
90 |
Refrigerant type |
|
R407C |
R407C |
R407C |
R407C |
Nb of refrigerant circuits |
no. |
2 |
2 |
2 |
2 |
Nb of compressors |
no. |
2 |
2 |
2 |
2 |
Expansion tank capacity |
l |
18 |
18 |
18 |
18 |
Water connector diameter
- male |
(inches) |
1" 1/2 |
1" 1/2 |
1" 1/2 |
1" 1/2 |
Sound pressure level (HS) at 10 m** |
dB(A) |
50 |
54 |
59 |
59 |
Sound power level (HS) |
dB(A) |
78 |
82 |
87 |
87 |
Net dimension (H./W./D.) |
mm |
1175x1955x1050 |
1175x1955x1050 |
1175x1955x1050 |
1425x1955x1050 |
Net weight |
Kg |
500 |
534 |
556 |
606 |
*Sound pressure: this level corresponds to that of a unit installed
outdoor (free sound field), on a reflective surface, with the
measurement being taken at a distance of 10 m.
COMPRESSOR (1)
Hermetic Scroll (1 for each refrigerant circuit), with acoustic
hooding and internal motor protection, mounted on anti-vibration
supports.
AIR / REFRIGERANT
EXCHANGER (2)
"L" exchanger with protection grill, alluminium fins on copper
tubes - Equipped with a temperature sensor for the condensation
pressure control.
AXIAL FAN (3)
1 fan (direct drive) for each refrigerant circuit, with heat
protection - Variable speed for the operation at low outdoor
temperatures.
High efficiency WATER / REFRIGERANT
EXCHANGER (4)
1 exchanger for each refrigerant circuit - Heat exchanger with
stainless steel brazed plates and heat insulation: it allows an
otpimized heat exchanger with a reduced quantity of refrigerant -
Refrigerated water and anti-freeze sensors.
REFRIGERANT CIRCUIT (5)
Refrigerant R407C -
Thermostatic pressure reducer -
Dehydrator filter -
High and Low pressure controllers.
INTGRATED HYDRAULIC
MODULE (6)
Circulating pump with insulation - Filling valve -
Manometer / Safety valve 3 bar -
Air vent - Control valve -
Expansion tank -
Water flow differential pressure controller.
SWITCHBOX (7)
Compliant with the standard EN 60 204-1 - Protection of the order
and power circuits by magnetothermal circuit breakers -
Phase sequence tester.
ELECTRONIC CONTROL KEYPAD/DISPLAY (8)
FRAME - OUTER COVER (9)
Made of coated sheet with strong thickness, polyester