5 models from 8,1 to 16,3 kW
-
Refrigerant R410A
-
The lowest sound levels on the market
-
Excellent E.E.R.
-
Complete hydraulic equipment
incorporated
-
Electronic control system
|
- Chillers intended for heating and air-conditioning
of residential and light-commercial buildings.
- Compact units to be installed outside.
- Ozone friendly refrigerant R410A
for the respect of the environment.
- Silent operation: the CHG Chillers have the
lowest sound level on the market.
- Scroll compressor with
sound insulation, high performance fin heat exchanger, axial fan motor with variable speed control
and heat protection, heat exchanger with AISI 316 stainless steel
plates and heat insulation, etc.
- Units ready to operate, with hydraulic
equipment incorporated : 3-speed circulating pump, expansion
tank, safety valve, air bleed valve, water pressure control,
hydraulic filter.
- Complete equipment: the CHG Chillers are
equipped with the following safety systems: high and low pressure
switch, water flow switch, anti-freeze safety.
- Proportional head pressure control.
- Electronic control by microprocessor (with keypad)
which optimizes the operation of the Chiller and grants the
following functions:
- Temperature control of hot water and cold water
- Self-adapting algorithm allowing the reduction
of the water volume (elimination of the buffer receiver vessel)
- Control of the operating parameters
- Automatic control of the circulating pump (anti-freeze and
anti-seize fonction)
- Counting of the operating time of compressor and circulator
- Defrosting adjusted according to the outdoor temperature
- Condensation pressure control
- Alarm management
- External communication via a serial inerface (Protocol
Modbus) (accessory)
- Output for controlling an additional
electronic device (not supplied).
- Easy access to all components.

MODELS |
CHG 8 |
CHG 11 |
CHG 15 |
CHG 17 |
Outdoor unit
Features |
230/1/50 |
CHG 085 F |
- |
- |
- |
400/3N/50 |
CHG 087 F |
CHG 117 F |
CHG 157 F |
CHG 177 F |
Unit |
Cooling |
Cooling |
Cooling |
Cooling |
Cooling capacity |
kW |
8,10 |
11,00 |
13,70 |
16,30 |
Power input
* single-phase/three-phase |
kW |
3,63 / 3,56* |
4,42 |
5,26 |
6,23 |
E.E.R. |
(kW/kW) |
2,28 |
2,49 |
2,6 |
2,62 |
Water flow |
m³/h |
1,40 |
1,91 |
2,34 |
2,81 |
Available head pump |
Kpa |
42 |
55 |
68 |
75 |
Refrigerant type |
|
R410A |
R410A |
R410A |
R410A |
Nb of refrigerant circuits |
no. |
1 |
1 |
1 |
1 |
Nb of compressors |
no. |
1 |
1 |
1 |
1 |
Expansion tank capacity |
l |
2 |
2 |
2 |
2 |
Water connector diameter
- male |
(inches) |
3/4" |
1" |
1" |
1" |
Sound pressure level (HS) at 10 m** |
dB(A) |
37 |
39 |
39 |
39 |
Sound power level (HS) |
dB(A) |
65 |
67 |
67 |
67 |
Net dimension (H./W./D.) |
mm |
735x1190x340 |
1235x1190x340 |
1235x1190x340 |
1235x1190x340 |
Net weight |
Kg |
87 |
120 |
123 |
130 |
**Sound pressure: this level corresponds to that of a unit installed
outdoor (free sound field), on a reflective surface, with the